Version 0.10.0
- Added package
Buildings.Airflow.Multizone with
models for multizone airflow and contaminant transport.
- Added the model
Buildings.Utilities.Comfort.Fanger
for thermal comfort calculations.
- Rewrote
Buildings.Fluid.Storage.BaseClasses.ThirdOrderStratifier,
which is used in
Buildings.Fluid.Storage.StratifiedEnhanced, to avoid
state events when the flow reverses. This leads to faster and more
robust simulation.
- In models of package
Buildings.Fluid.MixingVolumes, added nominal value for
mC to avoid wrong trajectory when concentration is
around 1E-7. See also https://trac.modelica.org/Modelica/ticket/393.
- Fixed bug in fan and pump models that led to too small an
enthalpy increase across the flow device.
- In model
Buildings.Fluid.Movers.FlowControlled_dp,
changed assert(dp_in ≥ 0, ...) to assert(dp_in ≥
-0.1, ...). The former implementation triggered the assert
if dp_in was solved for in a nonlinear equation since
the solution can be slightly negative while still being within the
solver tolerance.
- Added model
Buildings.Controls.SetPoints.Table
that allows the specification of a floating setpoint using a table
of values.
- Revised model
Buildings.Fluid.HeatExchangers.Radiators.RadiatorEN442_2.
The new version has exactly the same nominal power during the
simulation as specified by the parameters. This also required a
change in the parameters.
Generated at 2026-04-14T18:18:34Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos