Note: The packages whose name ends with Beta
are still being validated.
The following critical error has been fixed (i.e. error that can lead to wrong simulation results):
| Buildings.ThermalZones | |
Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange |
The model
Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange
had an error in the view factor approximation. The error caused too
much radiosity to flow from large to small surfaces because the law
of reciprocity for view factors was not satisfied. This led to low
surface temperatures if a surface had a large area compared to
other surfaces. The bug has been fixed by rewriting the view factor
calculation. |
The following improvements and additions have been made:
homotopy operator.Buildings.HeatTransfer.Buildings.Fluid.Actuators to
avoid having the flow coefficient k as an algebraic
variable. This increases robustness.Buildings.Fluid.Interfaces.StaticTwoPortHeatMassExchanger
to better handle zero mass flow rate.enthalpyOfCondensingGas and
saturationPressure in single substance media to allow
use of the room model with media that do not contain water
vapor.Buildings.Fluid.Sources.Outside to allow
use of the room model with media that do not contain water
vapor.