Reactive Current Injection Logic
This block implements the behavior of the switch mechanic for
reactive current injection, as specified in:
https://www.wecc.org/Reliability/WECC-Second-Generation-Wind-Turbine-Models-012314.pdf
- Setting tHoldIq to 0 results in abrupt ending of injection
after the voltage dip has ended.
- Setting tHoldIq to a negative value continues the injection
with the voltage-dependent injection for the absolute value of
tHoldIq seconds after the voltage dip has ended.
- Setting tHoldIq to a positive value continues the injection
with a set constant (IqFrzPu) for the absolute value of tHoldIq
seconds after the voltage dip has ended.
Generated at 2026-04-15T18:18:36Z by OpenModelicaOpenModelica 1.26.3 using