This sequence outputs AHU level effective outdoor air absolute
minimum and design minimum setpoints
VEffAbsOutAir_flow, VEffDesOutAir_flow
and the nomalized minimum setpoint
effOutAir_normalized when complying with California
Title 24 ventilation requirements. It is implemented according to
Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.
It calculates as below:
VSumZonAbsMin_flow and
VSumZonDesMin_flow from
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone
for the detailed description.VEffAbsOutAir_flow and
VEffDesOutAir_flow) are recalculated continuously
based on the mode of the zones being served.
VEffAbsOutAir_flow is the sum of
VZonAbsMin_flow for all zones in all zone groups that
are in occupied mode but shall be no larger than the absolute
minimum outdoor airflow VAbsOutAir_flow.VEffDesOutAir_flow is the sum of
VZonDesMin_flow for all zones in all zone groups that
are in occupied mode but shall be no larger than the absolute
minimum outdoor airflow VDesOutAir_flow.VEffAbsOutAir_flow at 50% signal to
VEffDesOutAir_flow at 100% signal. When there is no
CO2 sensor in any zone, the effective minimum outdoor airflow
setpoint should be equal to the
VEffDesOutAir_flow.