Outdoor air and return air damper position limits for units with
separated minimum outdoor air damper and differential pressure
control
Block that outputs the position limits of the return and outdoor
air damper for units with a separated minimum outdoor air damper
and differential pressure control. It is implemented according to
Section 5.16.4 of the ASHRAE Guideline 36, May 2020.
Differential pressure setpoint across the minimum outdoor air
damper
Open minimum outdoor air damper
Open minimum outdoor air damper when the supply air fan is
proven ON and the system is in occupied mode and the minimum
differential pressure set point is greater than zero. Damper shall
be closed otherwise.
Return air damper
- Return air damper minimum outdoor air control is enabled when
the minimum outdoor air damper is open and the economizer outdoor
air damper is less than a projected position limit, which is 5%
when supply fan speed is at 100% design speed proportionally up to
80% when the fan is at minimum speed.
- Return air damper minimum outdoor air control is disabled when
the minimum outdoor air damper is closed or the economizer outdoor
air damper is 10% above the projected position limit as determined
above.
- When enabled, the maximum return air damper set point is
modulated from 100% to 0% to maintain the differential pressure
across the minimum outdoor air damper at set point.
- August 29, 2023, by Hongxiang Fu:
Because of the removal of Logical.And3 based on ASHRAE
231P, replaced it with a stack of two Logical.And
blocks. This is for #2465.
- August 1, 2020, by Jianjun Hu:
First implementation.