Partial model that impliments cooling system for data centers
This is a partial model that describes the chilled water cooling
system in a data center. The sizing data are collected from the
reference.
Reference
- Taylor, S. T. (2014). How to design & control waterside
economizers. ASHRAE Journal, 56(6), 30-36.
Contents
- September 3, 2024, by Jianjun Hu:
Added plant on signal to control the pump speed. This is for
issue
3989.
- January 2, 2022, by Kathryn Hinkelman:
Passed the plaOn signal to the chilled water pump
control to turn them off when the plant is off.
- November 16, 2022, by Michael Wetter:
Corrected control to avoid cooling tower pumps to operate when
plant is off, because shut-off valves are off when plant is
off.
- November 1, 2021, by Michael Wetter:
Corrected weather data bus connection which was structurally
incorrect and did not parse in OpenModelica.
This is for issue
2706.
- October 6, 2020, by Michael Wetter:
Set val.use_inputFilter=false because pump worked
against closed valve at t=60 seconds, leading to negative
pressure at pump inlet (because pump forces the mass flow
rate).
- January 12, 2019, by Michael Wetter:
Removed wrong each.
- December 1, 2017, by Yangyang Fu:
Used scaled differential pressure to control the speed of pumps.
This can avoid retuning gains in PID when changing the differential
pressure setpoint.
- September 2, 2017, by Michael Wetter:
Changed expansion vessel to use the more efficient
implementation.
- July 30, 2017, by Yangyang Fu:
First implementation.